A.1 General technical data 
 
LOGO! 
292
 
Manual, 06/2014, A5E33039675 
Criterion 
Tested in accordance with 
Values 
LOGO! TDE (Text Display with 
Ethernet interfaces) 
Dimensions (WxHxD) 
Weight 
Installation 
 
 
 
128.2 x 86 x 38.7 mm 
Approx. 220 g 
Bracket mounting 
Climatic conditions 
Ambient temperature 
• 
Horizontal installation 
• 
Vertical installation 
Low temperature to IEC 
60068-2-1 
High temperature to IEC 
60068-2-2 
 
0 °C to 55 °C 
0 °C to 55 °C 
Storage/shipping 
 
- 40 °C to +70 °C 
Relative humidity 
IEC 60068-2-30 
From 10% to 95% no 
condensation 
Air pressure 
 
795 hPa to 1080 hPa 
Pollutants 
IEC 60068-2-42 
IEC 60068-2-43 
SO
2
 10 cm
3
/m
3
, 21 days 
H
2
S 1 cm
3
/m
3
, 21 days 
Ambient mechanical conditions 
Degree of protection 
 
IP20 for LOGO! Base Modules, 
expansion modules, and the 
LOGO! TDE excluding the TDE 
front panel 
IP65 for LOGO! TDE front 
panel 
Vibrations: 
IEC 60068-2-6 
5 Hz to 8.4 Hz 
(constant amplitude 3.5 mm) 
8.4 Hz to 150 Hz 
(constant acceleration 1 g) 
Shock 
IEC 60068-2-27 
18 shocks  
(half-sine wave 15 g/11 ms) 
Free fall (packaged) 
IEC 60068-2-32 
0.3 m 
Electromagnetic compatibility (EMC) 
Noise emission 
EN 55011/A 
EN 55022/B 
EN 50081-1 
(domestic area) 
Limit class B group 1 
Electrostatic discharge 
IEC 61000-4-2  
Severity 3 
8 kV air discharge 
6 kV contact discharge  
Electromagnetic fields 
IEC 61000-4-3 
Field strength 1 V/m and 10 
V/m 
HF currents on cables and cable 
shielding 
IEC 61000-4-6 
10 V 
Burst pulses 
IEC 61000-4-4Severity 3 
2 kV (supply and digital signal 
lines), 1 kV (analog signal lines) 
High-energy surge pulse (applies only 
to LOGO! 230 ...) 
IEC 61000-4-5Severity 3 
1 kV (power lines) symmetrical 
2 kV (power lines) asymmetrical 
Safety to IEC