Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 Data Sheet

Product codes
6ED1057-3BA00-0AA8
Page of 344
Technical data 
 
A.2 Technical data: LOGO! 230... 
 
LOGO! 
294
 
Manual, 06/2014, A5E33039675 
 
LOGO! 230RCEo 
LOGO! 230RCE 
Number of high speed inputs 
Input frequency 
• 
Normal input 
• 
High speed input 
 
• 
Max. 4 Hz 
• 
- - 
 
• 
Max. 4 Hz 
• 
- - 
Max. continuous permissible 
voltage 
265 VAC 
253 VDC 
265 VAC 
253 VDC 
Input voltage L1 
• 
Signal 0 
• 
Signal 1 
• 
Signal 0 
• 
Signal 1 
 
• 
< 40 VAC 
• 
> 79 VAC 
• 
< 30 VDC 
• 
> 79 VDC 
 
• 
< 40 VAC 
• 
> 79 VAC 
• 
< 30 VDC 
• 
> 79 VDC 
Input current at 
• 
Signal 0 
• 
Signal 1 
• 
Signal 0 
• 
Signal 1 
 
• 
< 0.05 mA AC 
• 
> 0.08 mA AC 
• 
< 0.06 mA DC 
• 
> 0.13 mA DC 
 
• 
< 0.05 mA AC 
• 
> 0.08 mA AC 
• 
< 0.06 mA DC 
• 
> 0.13 mA DC 
Delay time at 0 to 1: 
• 
120 VAC 
• 
240 VAC 
• 
120 VDC 
• 
240 VDC 
 
Delay time at 1 to 0: 
• 
120 VAC 
• 
240 VAC 
• 
120 VDC 
• 
240 VDC 
 
• 
Typ. 40 ms 
• 
Typ. 30 ms 
• 
Typ. 25 ms 
• 
Typ. 20 ms 
 
 
• 
Typ. 45 ms 
• 
Typ. 70 ms 
• 
Typ. 60 ms 
• 
Typ. 75 ms 
 
• 
Typ. 40 ms 
• 
Typ. 30 ms 
• 
Typ. 25 ms 
• 
Typ. 20 ms 
 
 
• 
Typ. 45 ms 
• 
Typ. 70 ms 
• 
Typ. 60 ms 
• 
Typ. 75 ms 
Line length (unshielded) 
max. 100 m 
max. 100 m 
Digital outputs 
Number 
Output type 
Relay outputs 
Relay outputs 
Electrical isolation 
Yes 
Yes 
In groups of 
Control of a digital input 
Yes 
Yes 
Continuous current I
th
 
Recommended range of 
application ≥ 100 mA at 
12 VAC/VDC 
Max. 10 A per relay 
Recommended range of 
application ≥ 100 mA at 
12 VAC/VDC 
Max. 10 A per relay