Puls DIMENSION YR40 DIN rails power supply din rail power supply U YR40.241 Data Sheet
Product codes
YR40.241
YR40.241
Y-Series
24-28V,
40A,
D
UAL
R
EDUNDANCY
M
ODULE
I
NDEX
Page
Page
The information presented in this document is believed to be accurate and reliable and may change without notice.
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
T
ERMINOLOGY AND
A
BREVIATIONS
PE and
symbol
PE is the abbreviation for Protective Earth and has the same meaning as the symbol
.
Earth, Ground
This document uses the term “earth” which is the same as the U.S. term “ground”.
T.b.d.
To be defined, value or description will follow later.
DC 24V
A figure displayed with the AC or DC before the value represents a nominal voltage with
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
standard tolerances (usually ±15%) included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
24Vdc
A figure with the unit (Vdc) at the end is a momentary figure without any additional
tolerances included.
tolerances included.
may
A key word indicating flexibility of choice with no implied preference
shall
A key word indicating a mandatory requirement
should
A key word indicating flexibility of choice with a strongly preferred implementation
1+1 Redundancy
Use of two identical power supplies in parallel to provide continued operation following most
failures in a single power supply. The two
power supply outputs should be isolated
each other by utilizing diodes or other
switching arrangements.
E.g. two 10A power supplies are needed to
achieve a 10A redundant system.
failures in a single power supply. The two
power supply outputs should be isolated
each other by utilizing diodes or other
switching arrangements.
E.g. two 10A power supplies are needed to
achieve a 10A redundant system.
2/17
N+1 Redundancy
Use of three or more identical power
supplies in parallel to provide continued
operation following most failures in a
single power supply. All power supply
outputs should be isolated each other by
utilizing diodes or other switching
arrangements. E.g.: To achieve a 40A redundant system, five 10A power supplies are needed in
a N+1 redundant system.
supplies in parallel to provide continued
operation following most failures in a
single power supply. All power supply
outputs should be isolated each other by
utilizing diodes or other switching
arrangements. E.g.: To achieve a 40A redundant system, five 10A power supplies are needed in
a N+1 redundant system.
N+1
Redundancy
1+1
Redundanc
y
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
IN 1
OUT
IN 2
IN 1
OUT
IN 2
IN 1
OUT
IN 2
IN 1
OUT
IN 2
Load
+
-
Load
+
-
Oct. 2010 / Rev. 1.0 DS-YR40.241-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany