Idec EMERGENCY STOP button XA / XW XW1E-BV413 3 Normally closed contact /1 Normally open contact XW1E-BV413R Leaflet

Product codes
XW1E-BV413R
Page of 1

XW1E Series  Emergency Stop Switch
  
Please confirm that the delivered product is what you have ordered. 

Safety Precautions 
xRead this instruction sheet and the catalog for the XW1E series emergency stop switches to make sure of correct operation before starting 
installation, wiring, operation, maintenance, and inspection. Make sure that the instruction sheet is kept by the end user.
x Turn off the power to the XW1E before starting installation, wiring, maintenance and inspection of the XW1E. Failure to turn power off may cause 
electric shock or fire hazard.   
x Use wires of an appropriate size to meet the voltage and current requirement. Using inappropriate wires may cause overheat, resulting in possible 
fire hazard. Also provide necessary protection against electric shock, otherwise electric shock or fire hazard may be caused. 
1.  Removing and Installing the Contact Block
Removing 
For easy removal of the contact block from the operator, first unlock 
the operator button. Push back the yellow bayonet ring with force 
until the latch pin clicks, then turn the contact block counterclockwise 
and pull out. Another method is to insert a small screwdriver into the 
latch hole to pull out the latch pin. While pulling the latch outward 
lightly, push back the yellow bayonet ring, then turn the contact block 
counterclockwise and pull out. D
Do  not  pull  out  the  latch  strongly. 
Excessive force will break the latch.
Note: When the contact block is removed, the monitor contact (NO 
contact) is closed.

Installing
For easy installation of the contact block onto the operator, first unlock 
the operator button. Align the small ʈ marking on the edge of the 
operator boss with the small ʆ marking on the bayonet ring. Hold the 
contact block, not the yellow bayonet ring. Press the contact block onto 
the operator and turn the contact block clockwise until the bayonet 
ring clicks. 













2.  Contact Ratings [Main Contact (NC) and Monitor Contact (NO)] 
Rated Insulation Voltage (Ui) 
300V 
Rated Current (Ith) 
5A 
Rated Operating Voltage (Ue) 
30V 
125V 
250V 
Resistive Load (AC-12) 

5A 3A 
AC
50/60Hz
Inductive Load (AC-15) 

3A 1.5A 
Resistive Load (DC-12) 
2A 
0.4A 
0.2A 
Main
Con
tact 
DC
Inductive Load (DC-13) 
1A 
0.22A 
0.1A 
Resistive Load (AC-12) 

1.2A 0.6A 
AC
50/60Hz
Inductive Load (AC-14) 

0.6A 0.3A 
Resistive Load (DC-12) 
2A 
0.4A 
0.2A 
Rated Operatin
g Cu
rren
Mo
nit
or 
Con
tact 
DC
Inductive Load (DC-13) 
1A 
0.22A 
0.1A 
3.  Internal LED Ratings 
Rated Voltage 
Operating Voltage 
Operating Current 
24V AC/DC 
24V AC/DC r10% 15 
mA 
4. Specifications 
Applicable Standard 
IEC6094751, EN6094751
IEC6094755, EN6094755
JIS C820151, UL508, CSA C22.2 No. 14 
Standard Operating 
Conditions 
Operating temperature 
      Nonilluminated:  25 to 60 qC (no freezing) 
   LED illuminated:  25 to 55 qC (no freezing) 
Relative humidity:    45 to 85 % RH (no condensation) 
Storage temperature:  45 to 80 qC (no freezing) 
Operating Force 
Push: 32 N 
Turn: 0.27 N㨯m
Pull: 21 
Minimum Direct 
Opening Force 
80 N 
Minimum Direct 
Opening Travel 
4.0 mm 
Maximum Travel 
4.5 mm 
Contact Resistance 
50 m: maximum (initial value) 
Insulation Resistance 
100 M: minimum (500V DC megger) 
Overvoltage Category 
II 
Impulse Withstand 
Voltage 
2.5 kV 
Pollution Degree 
Operating Frequency 
900 operations/hour 
Mechanical Life 
250,000 operations minimum 
Electrical Life 
100,000 operations minimum 
Shock Resistance 
Operating extremes:  100 m/s
2
Damage limits: 
1,000 m/s
2
Vibration Resistance 
Operating extremes:   5 to 55 Hz, amplitude 0.5 mm, 
acceleration 60 m/s
2
Damage limits: 
5 to 55 Hz, amplitude 0.5 mm, 
acceleration 60 m/s
2
Degree of Protection 
IP65 (panel front) 
Short-circuit
Protective Device 
250V/10A fuse (Type aM IEC602691/IEC602692)
Conditional Short
-circuit Current 
1,000 A 
Terminal 
Configuration 
Solder terminal 
PC board terminal 
Recommended 
Tightening Torque of 
Locking Ring 
2.0 N㨯m
Applicable Wire 
1.25 mm
2
maximum  (AWG16 maximum) 
Soldering Condition 
20 W/5 seconds or 260 qC/3 seconds 

5. Contact 
Arrangements 
(Bottom 
View) 
<Contact configuration with                              <Contact configuration with  
          a monitor contact (NO)>                                    main contacts (NC) only>



1NC: Terminals on the top 
1NC: Terminals on the right 
2NC: Terminals on the right and left 
2NC: Terminals on the right and left
                                                       
3NC: Terminals on the right, left and top 

6.  Mounting Hole Layout 







All dimensions in mm.





                                        www.idec.com                            No. B

791(1)   2003.8 
ٕ marking 
ً marking 
TOP marking
Ԙ
(Push) 
ԙ
(Turn clockwise)
Hold the contact block 
1
2
1
2
2
1
2
1
LED 
X1 
X2 
Right
Left
TOP
Right 
TOP
1
2
2
1
1
2
3
X1 X2 
LED 
Left 
4
!
ٌ 
Bayonet Ring 
Latch Hole 
ԙ
(Pull)
Ԛ
(Turn counterclockwise) 
Ԙ
(Pull out) 
ԙ
(Pull)
Ԙ
(Pull out) 
Ԛ
(Turn counterclockwise)
ޛWhen mounted on a panelޜ ޛWhen not mounted on a panelޜ