Finder 70.11.8.230.2022 Options: 1-phase mains monitoring (220 – 240 V/AC), undervoltage, overvoltage, over/under voltag 70.11.8.230.2022 Data Sheet

Product codes
70.11.8.230.2022
Page of 14
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
4b
UV
UVm*
Umax
Umax -H
LED 1
LED 2
LED 1
LED 2
4a
OV
OVm*
Umax
Umax -H
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
1
3a
3b
3d
3c
3e
3f
70.11
www.findernet.com
2
(1x6/2x4) mm
2
(1x10/2x12) AWG
(1x4/2x2.5) mm
2
(1x12/2x14) AWG
0.8 Nm
3
IP20
70.11.8.230.2022
U
N
: (220...240) V AC (50/60 Hz)
U
min
: 130 V AC
U
max
: 280 V AC
P: 2.6 VA / 0.8 W
1 CO (SPDT)
10 A 250 V AC
AC1                             2500 VA
AC15 (230 V AC)         750 VA
(230 V AC)         0.5 kW
DC1 (30 / 110 / 220)V   (10 / 0.3 / 0.12) A
(−20...+50) °C
IB7011001 - 08/12
4
4c
W
Wm*
1
~
M
70.11 RELÉ DE VIGILANCIA DE TENSIÓN MONOFÁSICA
DIMENSIONES
ESQUEMA DE CONEXIÓN 
11-14: contacto NA 
11-12: contacto NC
VISTA FRONTAL (detalle) 
3a
Selector de funciones 
UV
Subtensión sin memoria
UVm Subtensión con memoria
OV
Sobretensión sin memoria 
OVm Sobretensión con memoria 
W
Modo ventana sin memoria
Wm Modo ventana con memoria
3b
LED 1 (verde) 
3c
Regulación retardo a la intervención 
(T en el diagrama de funciones) (0.5 ...60)s
3d
LED 2 (rojo) 
3e
Regulación tensión máxima (220 ...270)V 
3f
Regulación tensión mínima (170 ...230)V
GRÁFICAS DE LAS FUNCIÓNES
4a
Subtensión (funciones UV y UVm)
4b
Sobretensión (funciones OV y OVm)
4c
Modo ventana (sobretensión y subtensión, funciones W y Wm)
NOTA
Histéresis (H en el diagrama de funciones): 5V. 
Tiempo de inicialización: 1s. 
Tiempo de restablecimiento: 0.5s.
Funcionamiento por lógica a seguridad positiva: el contacto se
abre cuando el valor medido pasa del valor seleccionado.
*
RESTAURAR LA MEMORIA 
La memoria se puede restaurar quitando la alimentación y 
realimentando de nuevo, o también girando el selector de 
funciones (3a) a una posición vecina y retrocediendo a la 
posición original.
1
2
3
ESPAÑOL