Finder 70.11.8.230.2022 Options: 1-phase mains monitoring (220 – 240 V/AC), undervoltage, overvoltage, over/under voltag 70.11.8.230.2022 Data Sheet

Product codes
70.11.8.230.2022
Page of 14
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
4b
UV
UVm*
Umax
Umax -H
LED 1
LED 2
LED 1
LED 2
4a
OV
OVm*
Umax
Umax -H
Umin +H
Umin
LED 1
LED 2
LED 1
LED 2
1
3a
3b
3d
3c
3e
3f
70.11
www.findernet.com
2
(1x6/2x4) mm
2
(1x10/2x12) AWG
(1x4/2x2.5) mm
2
(1x12/2x14) AWG
0.8 Nm
3
IP20
70.11.8.230.2022
U
N
: (220...240) V AC (50/60 Hz)
U
min
: 130 V AC
U
max
: 280 V AC
P: 2.6 VA / 0.8 W
1 CO (SPDT)
10 A 250 V AC
AC1                             2500 VA
AC15 (230 V AC)         750 VA
(230 V AC)         0.5 kW
DC1 (30 / 110 / 220)V   (10 / 0.3 / 0.12) A
(−20...+50) °C
IB7011001 - 08/12
4
4c
W
Wm*
1
~
M
PORTUGUÊS
70.11 RELÉ DE MONITORAMENTO MONOFÁSICO
OUTLINE DRAWING
ESQUEMA DE LIGAÇÃO
11-14: contato NA
11-12: contato NF
VISTA FRONTAL (detalhes)
3a
Seletor de funções
UV
Subtensão sem memória
UVm Subtensão com memória
OV
Sobretensão sem memória
OVm Sobretensão com memória
W
Faixa de tensão sem memória
Wm Faixa de tensão com memória
3b
LED 1 (verde)
3c
Tempo de retardo ajustável (T no diagrama de funções) (0.5...60s)
3d
LED 2 (vermelho)
3e
Ajuste da tensão máxima (220...270)V
3f
Ajuste da tensão miníma (170...230)V
FUNÇÕES
4a
Subtensão (funções UV e UVm)
4b
Sobretensão (funções OV e OVm)
4c
Faixa de tensão (sobretensão e subtensão, funções W e Wm)
NOTA
Histerese (H no diagrama de funções): 5V.
Tempo de inicialização: 1s.
Tempo de reestabelecimento: 0.5s.
Lógica de segurança positiva - O contato do relé abre quando o
valor medido estiver fora da faixa aceitável.
*
RESET DA MEMÓRIA
Para resetar, é necessário retirar a alimentação e liga-la novamente,
outra forma é girar o seletor de funções (3a) primeiro para uma 
posição adjacente e depois voltar para a posição original.
1
2
3
4