4.6.1  Commissioning mode/self test 
General 
The charging station can be placed into a commissioning mode for supporting the initial sys-
tem test. During this, a self test of the device is performed (interlocking, contactor activation, 
current measurement, etc.) and the result is displayed.  
After successful test without connected vehicle, the contactor is switched for limited time in 
order to facilitate the initial tests. A normal charging procedure is not possible in commission-
ing mode. The interlocking of the connector socket is activated to prevent a cable from being 
plugged in. 
 
 
Activating the commissioning mode 
► 
Set the IBN DIP-switch DSW2.8 to ON (see "DIP-switch settings"). 
► 
Perform a reset of the charging station. To do this press the [Service button] for 
1 second
 or switch the power supply voltage off/on. 
 
The commissioning mode is now activated and is indicated by the orange status LED 
(lights continuously). 
► 
You now have the option for approximately 5 min. to contact with standard test probes 
using the measuring device ( e.g. Astaco® test probes from BEHA) and to perform the 
necessary tests (see chapter "Safety checks"). 
 
After 5 min. have elapsed, the contactor is deactivated in the charging station is shut 
down. 
 
 
Deactivating commissioning mode 
► 
Set the IBN DIP-switch DSW2.8 to OFF again. 
► 
Perform a reset of the charging station. To do this, press the [Service button] for 
1 second
 or switch the power supply voltage off/on. 
 
The charging station starts up again in normal mode and is ready for operation.