Tripp Lite 3.2-3.8kW Single-Phase Switched PDU, 200-240V (20-C13 & 4-C19), C20/L6-20P Cable, 0U Vertical, 70 in. PDUMV20HVNET Data Sheet

Product codes
PDUMV20HVNET
Page of 3
10/100 Mbps auto-sensing 
Real-time clock backup maintains the time of day and date even if the PDU is not powered on
Tiered access privileges allow an administrator and a guest to login via web browser
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, SNMPv3, Telnet, SSH, FTP, DHCP, BOOTP, NTP
protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets keep vital network equipment plugged in and continuously powered 
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications
 Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Specifications
General Info
RoHS
Y
OVERVIEW
Style
Vertical Rackmount
PDU Type
Switched
OUTPUT
Output Capacity Details
3.3kW (208V input), 3.5kW (220V input), 3.7kW (230V input), 3.8kW (240V input), 3.2kW (200V input); 20A
maximum (agency de-rated to 16A continuous)
Frequency Compatibility
50 / 60 Hz
Output Receptacles
(20) C13; (4) C19
Output Nominal Voltage
200-240V nominal, single phase
Outlet Type
IEC-C13, IEC-C19
Customized Load Management
Receptacles
Each outlet is individually controllable via remote interface
INPUT
PDU Input Voltage
200; 208; 220; 230; 240
Maximum Input Amps
20
Maximum Input Amps Details
Agency de-rated to 16A continuous
Input Connection Type
C20 inlet accepts included L6-20P input cable
PDU Plug Type
NEMA L6-20P; IEC-320 C20
Input Cord Length (ft.)
10
Input Cord Length (m)
3
2 / 3