Tripp Lite 5kW Single-Phase ATS/Switched PDU, 208V (16 C13, 2 C19 & 1 L6-30R) 2 L6-30P Input Cords, 2U Rack-Mount PDUMH30HVATNET Data Sheet

Product codes
PDUMH30HVATNET
Page of 4
Recommended Electrical Service
30A 208V
Maximum Input Amps
30
Maximum Input Amps Details
Agency rated to 24A continuous
Input Connection Type
Two labelled L6-30P inputs support Primary and Secondary input connections
PDU Plug Type
NEMA L6-30P
Input Cord Length (ft.)
10
Input Cord Length (m)
3
Input Phase
Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Digital display reports output amps in 4 separately metered loading segments (BANK 1: Outlets #1-9; BANK 2:
Outlets #10-18; BANK 3: Outlet #19), whole-PDU output kW load level and input voltage on primary and secondary
input lines
Front Panel LEDs
19 LEDs display power on/off status for each outlet, plus 2 LEDs for power status on Primary and Secondary input
connection and three additional LEDs to label the displayed numeric value as Amps, kW or Voltage
Switches
ENTER and MODE switches toggle the digital display to show output amps (Banks 1-4), total kW output and input
voltage (primary, secondary)
PHYSICAL
Shipping Dimensions (hwd / in.)
7.8 x 16.7 x 19.9
Shipping Dimensions (hwd / cm)
19.8 x 42.4 x 50.5
Shipping Weight (lbs.)
19.3
Shipping Weight (kg)
8.8
Unit Dimensions (hwd / in.)
3.5 x 17.5 x 12.5
Unit Dimensions (hwd / cm)
8.8 x 44.5 x 31.8
Unit Weight (lbs.)
13.7
Unit Weight (kg)
6.3
Material of Construction
Metal
Form Factors Supported
2U rackmount
PDU Form Factor
Horizontal (1U, 2U, etc)
ENVIRONMENTAL
Storage Temperature Range
5 to 122F (-15 to 50C)
Relative Humidity
5 to 95% (non-condensing)
Operating Elevation (ft.)
0-10,000
Operating Elevation (m)
0-3000
COMMUNICATIONS
3 / 4