Bosch Appliances Home Security System D7412G User Manual

Page of 142
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED
EN | 111
Bosch Security Systems | 1/04 | 47775E
S## Door 1 [through 8]
Default: No
Yes
Enable the reporting
of No Entry Events
for Door #.
24
No Entry Events Off: The control
panel can log No Entry Events
when an invalid token is detected
for a specific door. No Entry
Events include No Entry-Secured,
No Entry-Interlock, No Entry-
Unknown ID, and No Entry-Level.
These events can be directed to
print at a local printer or report
remotely through phone routing.
This sked disables No Entry
Events to be reported for Door #.
Selection: Yes or No
This parameter disables the reporting
of No Entry Events for Door #.
No
Do not enable the
reporting of No
Entry Events for
Door #.
Sked Functions 28 and 29 are available only in firmware versions 6.30 and higher. RPS version 3.5 and
RADXSKED handler version 1.02 and higher must be used to program these new skeds.
28
Expanded Off-Normal Test Report: To generate this event, one or more points must be in an off-normal
state at the time the sked executes. In addition, any system trouble that is active also generates an Expanded
Off-Normal Test Report. Expanded Off-Normal Test Reports include the Off Normal Test Report Event as
well as the supplementary event at the time the report is generated.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and
the Off-Normal Test Report is not sent.
To meet UL 864 daily Test Report requirements (when using two phone lines) you must still use Sked
Function Code 9, Test Report and program it to occur on a daily basis as per AHJ requirements.
29
Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent
when any point is in the off-normal state from any area, but only sends the Off Normal Test Report Event. In
addition to this, any system trouble that is active also generates a Non-Expanded Off-Normal Test Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated and
the Non-Expanded Off-Normal Test Report is not sent.
To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use Sked
Function Code 9, Test Report and program it to occur on a daily basis as per AHJ requirements.