Bosch Appliances Home Security System D7412G User Manual

Page of 142
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS
EN | 132
Bosch Security Systems | 1/04 | 47775E
 D# Interlock Point
Default:
Blank
Selection:
Blank, 1 to 127, 129 to 247
1 to 127,
129 to 247
The point number assigned to the
Interlock point. Points 128 and 248 are
reserved by the control panel for
internal use.
Blank
There is no point number assigned to
the Interlock point.
Enter the Interlock point number. This point, when
faulted, prevents the door controller from allowing
access upon a valid ID read or door request.
Do not assign this point to another Door point. You
may assign it to another controller. One Interlock
point prevents multiple controllers from activating.
Door points must be programmed as
Perimeter points. If a 24-hour point type is
required for the Door point, you can use a
Perimeter point type with a Point
Response of 9 to C. Also, the debounce
count must be set to 4 in Point
Assignments.
The Interlock point is considered in a
normal state if it is bypassed, swinger
bypassed, or forced armed. This results in
normal access even if the door is left open.
D# Auto Door?
Default:
No
Selection:
Yes or No
Yes
When the area assigned in 
D# Entry
Area #
 is disarmed, the door is in the
unlocked state. When that area is
armed, the door returns to the locked
state.
No
Door state is not affected by the armed
state of the area.
Use this program item to automatically unlock the
door (latched, shunt, and strike) when the entry area
is disarmed. The door re-locks upon Master or
Perimeter Arming the area.
The unlocked state cannot be overridden
manually.
Doors that are activated by Fire Unlock
must be returned to normal using the Door
Control function on the control center.
D# Fire Unlock?
Default:
No
Selection:
Yes or No
Yes
Relay activates and shunt is applied for
the door contact automatically upon a
Fire Alarm.
No
Door remains in its current mode upon
a Fire Alarm.
Use this program item to activate the relay for the
door strike and shunt the door zone automatically
upon a Fire Alarm. This feature overrides a Secure
Door state, Locked Door state, Auto Door, and an
Interlock Faulted point. The relay activates for all
doors with this prompt programmed Yes when a
Fire Alarm occurs in any area. Relays that are
activated by Fire Unlock can only be returned to
normal through the command center using the Door
Control function.
This unlocks the door regardless of the
armed state.
Each fire alarm that is generated causes a
Door Unlocked – Automatic Event.
D# Disarm on Open?
Default:
Yes
Selection:
Yes or No
Yes
The area disarms only after the door
was opened for a user with a valid
disarm level.
No
The area disarms whether or not the
door was opened as soon as a user with
a valid disarm level presents a valid
token/card.
Use this program item to determine whether the
door needs to be physically opened prior to
disarming the area upon a valid access request. The
user initiating the access request needs access levels
that allow disarming with ID.