D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS
EN | 83
Bosch Security Systems | 1/04 | 47775E
P## Entry Delay
Default:
See 
Program Record Sheet
Selection:
5 seconds to 600 seconds
Use this option to enter the amount of entry delay
time that a user has after faulting a Controlled point
(
P## Type 1, 2, 3
) with a delayed response (D)
(
P## Pt Response
) of 4, 5, 6, 7, or 8. 
DISARM NOW
displays for the duration of the time programmed
when the point is faulted in the delay condition.
0101
0101
0101
Beginning with firmware revision 6.30
and higher, the D1255 alternates
between 
DISARM NOW
 and the point text
of the point that caused the area to go
into entry delay.
If this time expires before disarming, or if the point
is faulted to an instant response (I), an alarm occurs.
0101
0101
0101
Make entries in 5 second increments. The
programmer does not allow off-increment
entries.
If another Perimeter or Interior Follower
Delay point trips while the area is already
in entry delay, the control panel adjusts the
delay time to the Delay point with the least
amount of delay time.
Use P## Type 3 Interior Follower to
program points that do not go into instant
alarm the user must fault in order to get to
the command center and disarm during
the entry or exit delay period.
P## Ent Tone Off
Default:
No
Selection:
Yes or No
Yes
Disable entry delay tone when this
point is faulted to the delay response.
No
A tone sounds at command centers
when this point initiates entry delay.
This option enables/disables the entry delay warning
tone for this point.
Do not set points to No if they are actually
used to notify the user to disarm the
system. The possibility of false alarms
increases if the entry delay warning is not
used.
0101
0101
0101
Entry Tone can also be turned off when
programming your CC Entry Tone, in
Section 2.10 Command Center, which
allows you to manage the tone by
command center.
You may want to disable the entry tone in
high security applications where you do
not want to annunciate entry delay.
P## Silent Bell
Default:
No
Selection:
Yes or No
Yes
Activate the Silent Alarm relay when
this point goes into alarm. Command
centers do not sound the alarm tone
for Non-fire points.
No
Activate either the Fire Bell relay or
Alarm Bell relay and sound the alarm
tone at command centers when this
point goes into alarm. If this is a Fire
point, it activates the Fire Bell relay
programmed in Relay Parameters.
Otherwise, it activates the Alarm Bell
relay. The amount of time and pattern
of the relay activation is programmed
by area in Bell Parameters.
If you want this point to eventually ring the
bell because the message failed to reach
the central station receiver, program P##
Audible After 2 Failures
 as Yes.
P## Ring Til Rst
Default:
No
Selection:
Yes or No
Yes
The relay programmed to provide fire
alarm output for this point cannot be
de-activated until the point restores to
normal.
No
The relay programmed to provide fire
alarm output for this point can be de-
activated before the point restores to
normal.
Use this option to determine if the bell continues to
ring until the Fire Bell time expires. The point
returns to a normal condition when the user
acknowledges the alarm to silence the bell.