D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED
EN | 95
Bosch Security Systems | 1/04 | 47775E
5.0
RADXSKED
5.1
Windows
Use this programming module to define the
windows for Opening and Closing and User Access.
5.1.1
Opening and Closing
Use these windows to set a schedule for disarming
and arming. The disarming and arming schedules
provide several independent features:
 
Suppress normal Opening and/or Closing
Reports when 
A# Disable O/C in Windows
 is
programmed Yes.
 
Generate a Fail to Open Report if the area is not
disarmed on schedule when 
A# Fail To Open
is programmed Yes.
 
Provide a warning tone and a 
PLEASE CLOSE
NOW
 display at the command center when it is
time to arm the area.
 
Generate a Fail to Close Report if the area is not
armed on schedule when 
A# Fail To Close
 is
programmed Yes.
 
Automatically arm the area at the end of the
Closing Window when 
A# Auto Close
 is
programmed Yes.
Opening and closing schedules can be set up
independently. For example, if you only want to use
features provided by Closing Windows, leave times
blank in the Opening Windows prompts and
program Closing Window times.
A worksheet is provided at the end of this section for
your convenience. Following the worksheet are
examples of how to program Opening and Closing
Windows for particular applications (see Table 35
through Table 39.
About the Program Record Sheet: A column
labeled Sked # is found on the Program Record Sheet
provided with the control panel. These numbers
appear in D6500/D6600 reports and local printer
reports when the window Begin Time executes.
Window selections 1 through 8 correspond with odd
numbered Skeds 41 through 55 for Open Window
and correspond with even numbered Skeds 42
through 56 for Close Window. For example, when
the Opening Window for Window 1 executes, a
Sked 41 Executed Event is generated. See Table 31.
Table 31: Window Selections
Selection
Sked #
Window
Sked #
Windo
w
1
41
Open
42
Close
2
43
Open
44
Close
3
45
Open
46
Close
4
47
Open
48
Close
5
49
Open
50
Close
6
51
Open
52
Close
7
53
Open
54
Close
8
55
Open
56
Close
Window
Default:
1
Selection:
1 to 8
Enter the window number you want to program.
W# Sunday
Default:
No
Selection:
Yes or No
Yes
Activate this window on Sundays.
No
Do not activate this window on
Sundays.
This prompt, and the next six day of the week
prompts, select the days of the week the Opening
and/or Closing Windows are active.
Exceptions:
To prevent the windows from activating on certain
days of the year, program 
Xept Holiday
 Yes, and
enable at least one Holiday Index. When 
Xept
Holiday
 is Yes, the window executes on the days of
the week programmed unless the Holiday Index
designates the date as a holiday.
If Opening and/or Closing Windows are only
needed on certain days of the year, do not program
the windows to execute on any days of the week.
Instead, program 
Xept Holiday
 No and select a
Holiday Index with the days of the year you want
the window to be active.