Utica Boilers MGB Series II/MGC Series Installation Instruction

Page of 32
12
 WARNING
Do not connect boiler to any portion of 
mechanical draft system operating under 
positive pressure.
!
     
Minimum Vent Pipe Clearance
Wood and other combustible materials must not be 
closer than 6” from any surface of single wall metal 
vent pipe. Listed Type B vent pipe or other listed 
venting systems shall be installed in accordance with 
their listing.
Removing Existing Boiler From Common 
Venting System
When an existing boiler is removed from common 
venting system, common venting system is likely to be 
too large for proper venting of appliances remaining 
connected to it.
At time of removal of existing boiler, following steps 
shall be followed with each appliance remaining 
connected to the common venting system placed 
in operation, while other appliances remaining 
connected to common venting system are not in 
operation.
1. 
Seal any unused openings in the common venting 
system.
2. 
Visually inspect the venting system for proper 
size and horizontal pitch and determine there is 
no blockage or restriction, leakage, corrosion and 
other deficiencies which could cause an unsafe 
condition.
3. 
Insofar as is practical, close all building doors 
and windows and all doors between the space in 
which the appliances remaining connected to the 
common venting system are located and other 
spaces of the building. Turn on clothes dryers 
and any appliance not connected to the common 
venting system. Turn on any exhaust fans, such 
as range hoods and bathroom exhausts, so they 
will operate at maximum speed. Do not operate a 
summer exhaust fan. Close fireplace dampers.
7 - CHIMNEY AND VENT PIPE CONNECTION
4. 
Place in operation the appliance being inspected. 
Follow the lighting instructions. Adjust thermostat 
so appliance will operate continuously.
5. 
Test for spillage at the draft hood relief opening 
after 5 minutes of main burner operation. Use 
the flame of a match or candle, or smoke from a 
cigarette, cigar or pipe.
6. 
After it has been determined that each appliance 
remaining connected to the common venting 
system properly vents when tested as outlined 
above, return doors, windows, exhaust fans, 
fireplace dampers and any other gas-burning 
appliance to their previous conditions of use.
7. 
Any improper operation of the common venting 
system should be corrected so the installation 
conforms with the National Fuel gas Code, ANSI 
Z223.1/NFPA 54. When re-sizing any portion of 
the common venting system, the common venting 
system should be re-sized to approach the 
minimum size determined using the appropriate 
tables in Chapter 13 of the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54.
 WARNING
Boiler and venting installations shall be 
performed by a qualified expert and in 
accordance with the appropriate manual. 
Installing or venting boiler or other gas 
appliance with improper methods or materials 
may result in serious injury or death due to 
fire or to asphyxiation from poisonous gases 
such as carbon monoxide with is odorless and 
invisible.
!