Utica Boilers MGB Series II/MGC Series Installation Instruction

Page of 32
14
9 - GAS SUPPLY PIPING
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not 
use any phone in your building.
• Immediately call your gas supplier from a 
neighbor’s phone.  Follow gas supplier’s 
instructions. 
• If you cannot reach your gas supplier, call 
the fire department.
!
  
CHECK GAS SUPPLY
Gas pipe to your boiler must be correct size for 
length of run and for total BTU per hour input of all 
gas utilization equipment connected to it. See Table 
5 for proper size. Be sure your gas line complies with 
local codes and gas company requirements.
CONNECTING THE GAS PIPING
Gas line enters boiler from right side.
• Use piping materials and joining methods 
acceptable to authority having jurisdiction.  In 
absence of such requirements National Fuel gas 
Code, ANSI Z223.1/NFPA 54
•  Use pipe joint compound suitable for LP gas on 
male threads only.
•  Use ground joint unions.
•  Install sediment trap upstream of gas controls.
•  Use two pipe wrenches when making connection 
to gas valve to keep it from turning.
•  Install manual shut-off valve in vertical pipe about 
5 feet above floor.
•  Tighten all joints securely.
•  Propane gas connections should only be made by 
licensed propane installer.
•  Two-stage regulation should be used by propane 
installer.
•  Propane gas piping should be checked out by 
propane installer.
CHECKING GAS PIPING
DANGER
Fire Hazard.  Do not use matches, candles, 
open flames, or other methods providing 
ignition source. Failure to comply will result in 
death or serious injury.
!  
Pressure test boiler and gas connection before placing 
boiler in operation.
•  Pressure test over 1/2 psig (3.5 kPa).  Disconnect 
boiler and its individual gas shutoff valve from gas 
supply system.
•  Pressure test at 1/2 psig (3.5 kPa) or less.  Isolate 
boiler from gas supply system by closing manual gas 
shutoff valve.
•  Locate leakage using gas detector, noncorrosive 
detection fluid, or other leak detection method 
acceptable to authority having jurisdiction.  Do 
not use matches, candles, open flames, or other 
methods providing ignition source.
•  Correct leaks immediately and retest.
NATURAL GAS
Pipe Capacity - BTU Per Hour Input 
Includes Fittings
Length of 
Pipe - FT
½”
¾”
1”
1¼”
20
92,000
190,000
350,000
625,000
40
63,000
130,000
245,000
445,000
60
50,000
105,000
195,000
365,000
PROPANE GAS
Pipe Capacity - BTU Per Hour Input 
Includes Fittings
Length of 
Pipe - FT
Copper Tubing *
Iron Pipe
⅝”
¾”
½”
¾”
20
131,000
216,000
189,000
393,000
40
90,000
145,000
129,000
267,000
60
72,000
121,000
103,000
217,000
* Outside diameter
  Measure length of pipe or tubing from gas meter or 
propane second stage regulator.
Table 5 - Gas Pipe Sizes
Figure 11 - Gas Piping