System Sensor PDRP-1001 User Manual
1. Product Description
Specifications
12
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Specifications
AC Power
PDRP-1001 and PDRP-1001A: 110/120 VAC, 50/60 Hz, 1.2 amps
PDRP-1001E: 220/240 VAC, 50/60 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
PDRP-1001E: 220/240 VAC, 50/60 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 18 AH.
Maximum Battery Capacity: 18 AH.
Note: Batteries larger than 12 AH require Notifier BB-17 or other UL-listed external battery cabinet.
Initiating Device Circuits
Power-limited circuitry
Operation: Style B (Class B) or Style D (Class A)
Normal Operating Voltage: 24 VDC (ripple = 1.0V p-p)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
Normal Operating Voltage: 24 VDC (ripple = 1.0V p-p)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
Notification Appliance and Releasing Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation
ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).
ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).
Resettable Power
Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p.
Nonresettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector
power). Maximum ripple voltage: 1.0 V p-p.
power). Maximum ripple voltage: 1.0 V p-p.
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available
to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.
to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.