Optional Modules
2. Installation
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
25
Setup and Configuration
Transmitter Module - 4XTM
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module 
as shown below. Polarities shown in activated positions.
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing 
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is 
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the 
Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring 
Requirements" on page 17.  
Figure 15  4XTM Configuration
TB1
TBL
J1
J2
4XTMF
.cd
r
TBL Jumper
Disconnect Switch
Disconnect LED
Remote Alarm (Power-limited)
Remote Trouble (Power-limited)
Municipal Box (Nonpower-limited)
No Connection
+

+
+