System Sensor PDRP-1001 User Manual

Page of 56
2. Installation
Optional Modules
26
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
Zone Relay Module - 4XZM
Note: The PAR-3 includes one (1) Zone Relay Module (4XZM).
Relay #1 through #4 on this module will activate with outputs #1 through #4.
For non-latching (silenceable) relay operation, cut the jumper “LATCH”.  If this jumper is left intact, the 
relays will latch upon activation.  To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label, 
located on the door of the control panel.   
Figure 16  Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring 
Requirements" on page 17.
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of 
dry contacts to maintain the required separation between circuit types.
• If this module is used to drive both nonpower-limited and power-limited relays that are next to each 
other, refer to the figure below which shows the one allowable arrangement. 
Figure 17  Mixing Power-Limited and Nonpower-Limited Circuits
TB1
LATCH
DISABLE
J2
Disable Switch
“Latch” Jumper
4X
ZMF
.cdr
Power-Limited 
Circuit
Nonpower-Limited 
Circuit
MS44
--
4xzm
f1
.cd
r
No Connection