System Sensor PDRP-1001 User Manual

Page of 56
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
31
3. System Operation
System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged 
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily. 
Figure 21  System Status LEDs
AC Power  - Green LED that illuminates steadily to indicate presence of AC power.
System Alarm - Red LED that  flashes when an alarm occurs.
Release - Red LED that illuminates steadily when release occurs. After the Discharge Timer has expired, 
the LED will flash.
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch) 
on 
IDC
 4.
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with 
optional boards.
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits (notification and 
releasing).
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been 
pushed after an alarm.
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
The following LEDs are located below the main panel and are visible only when the panel door is open.
Battery Fail (
BATT
) - Yellow LED that illuminates steadily on motherboard when battery is low or not 
detected.
Ground Fault (
EARTH
) - Yellow LED that illuminates steadily on motherboard during a ground fault 
condition.
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor 
failure.
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
SYSTEM
RESET
AC POWER
SYSTEM
ALARM
RELEASE
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
ZONE 1
ZONE 2
WATERFLOW
SUPERVISORY
PE
M2
-p
an
el
1.
cdr
BATT   EARTH
MICRO 
FAIL
System 
Status 
LEDs