3. System Operation
Control Switches
32
PDRP-1001 Instruction Manual  PN 50734:D0  04/06/01
Control Switches
 
Figure 22  Control Panel Switches
Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories.  The panel has 
alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate 
steadily on TONE SILENCE and the piezo turns off.  A second trouble will resound the piezo.  Trouble 
conditions are self-restoring. Alarms latch and require pressing SYSTEM RESET to clear.  Unless the unit 
is set for non-latching supervisory service, supervisories latch and require pressing SYSTEM RESET to 
clear.  The piezo has three tones for different conditions (see "Piezo" on page 33). 
Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will 
silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits (not 
the Releasing Circuits)
.  The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function 
and requires pressing SYSTEM RESET to clear.
Note: Releasing Circuits will turn off only if Discharge timer criteria is satisfied (see "Setting Mode of Operation" on 
page 28).
Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also 
activates the System Alarm Relay.  This is a latching function.  Pressing ALARM SILENCE silences the 
NACs and System Alarm Relay, and lights the Alarm Silenced LED.  Pressing SYSTEM RESET returns 
the system to normal.
System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and 
optional boards and will clear any activated output circuits.  If any alarm or trouble still exists after reset, 
they will reactivate the panel.  Holding SYSTEM RESET down will perform a LAMP TEST function and 
will activate the piezo sounder.
Zone Status LEDs
The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM 
SILENCE), at which point the LED(s) will illuminate steadily.  
Figure 23  Zone Status LEDs
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
SYSTEM
RESET
M
S
44
-p
an
el
2.
cdr
ZONE 1
ZONE 2
WATERFLOW
SUPERVISORY
PE
M2
-p
an
e
l2.
cd
r
Alarm LED
Trouble LED
Not Used