Symmetricom 1000 User Manual

Page of 224
097-58001-02 Revision G – April 2008
TimeProvider User’s Guide 113
Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference
ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
Sample Commands
ED-SYNC::PRS:::QLEVEL=1;
ED-SYNC::INP1:::QLEVEL=1;
ED-SYNC::INP2:::QLEVEL=1;
This series of commands sets the QLEVEL for all inputs to the same level; if you 
also provision the PRIORITY level to the same value, then you have set up a 
non-revertive switching strategy.
Autonomous Message
TP-SSU 03-10-24 10:54:44
A 1183 REPT EVT
“PRS,EQPT:NA,QLEVEL,NSA,003-10-24 10-54-44:\"USER 
ASSIGNED QUALITY LEVEL HAS CHANGED,1\””
;
Setting the Input Priority Level
The PRIORITY level works together with the QLEVEL parameter (described in 
, on page 112) to determine the switching strategy. 
The PRIORITY level is the second factor the TimeProvider uses to determine which 
input to use when the original primary input becomes unavailable.
Use the ED-SYNC command to set the PRIORITY level of the selected reference.
ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
<aid>
<keyword>
<value>
Description
Default value
PRS
INPp (p = 1 | 2)
GPS
QLEVEL
1 = PRC
2 = UNK/STU
3 = TYPE II/ST2
4 = TYPE I
5 = TYPE V/TNC
6 = TYPE III/ST3E
7 = TYPE IV/ST3
8 = G.813OPT3/SMC
9 = DUS
Sets the Quality 
Level for the 
specified input
2
<aid>
<keyword>
<value>
Description
Default value
PRS
INPp (p = 1 | 2)
GPS
PRIORITY
2 | 3 | 4
Sets the priority for 
the selected input
GPS = 1
PRS = 2
INP1 = 3
INP4 = 4