Symmetricom 1000 User Manual

Page of 224
097-58001-02 Revision G – April 2008
TimeProvider User’s Guide
91
Chapter 4 Provisioning the TimeProvider
Setting Communications Parameters
Setting Ethernet Parameters
Set up the Ethernet port, if you are using it, by following the procedure in 
Setting User Security
Set up the user security (usernames and passwords), if you are using it, by 
following the procedure in 
Setting Communications Parameters
If you want to change the communications parameter values, use the ED-EQPT 
command. The following sections describe the commands for performing each 
individual task. For detailed information on the ED-EQPT command, see the 
TimeProvider TL1 Reference Guide. Record the values you provision in 
.
Setting RS-232 Parameters
This section describes how to set the baud rate, the handshaking mode, and echo 
modes on the local and remote ports. The default values are 9600 baud, No flow 
control, echo mode disabled, tidquiet disabled.
Setting the Baud Rate
Use the ED-EQPT command to provision the baud rate on the Local or Remote port.
ED-EQPT:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
Sample Command
ED-EQPT::COML:TS1000::BAUD=9600;
This command sets the local Craft communications port to 9600 baud.
Normal Response
TIMEPROVIDER 03-10-24 10:10:25
M
TS1000 COMPLD
;
<aid>
<keyword>
<value>
Description
Default value
COMp
p = L | R
BAUD 
2400 | 9600 | 19200 | 
28800 | 38400 | 57600 | 
115200
Baud rate
9600