Siemens TV Converter Box G120 User Manual

Page of 147
 
 
 
 
 
 
 
    
Automation and Drives - SCE 
 
 
 
 
T I A  Training Document
 
Page 42 of 147 
 Module  
 
     H01 
Issued: 02/2008 
  Frequency Converter SINAMICS G120 on PROFIBUS DP and PROFINET 
Preface         Notes         Startup with PROFIBUS         Startup with PROFINET         Program Example 
 
3.5.1.2 
Parameters that are visible/Parameters that can be changed 
 
There are two main types of parameters: 
Parameters that can be changed are marked P…. 
Parameter, that can only be read are marked r…. 
 
Not every parameter can always be viewed/modified. This can be influenced with the following 
parameters: 
 
P0004 Parameter Filter 
 
Filters parameters according to functionality, to specify settings during startup. 
The following filter settings can be made: 
0: All parameters 
2: Converter 
3: Motor 
4: Speed sensor 
5: Technological application/units 
7: Commands, Digital I/O 
8: AI and AO 
10: Setpoint channel/RFG 
12: Drive characteristics 
13: Motor control 
19: Motor identification 
20: Communication 
21: Messages/warnings/monitoring 
22: Technology controller 
 
P0003 User Access Level 
 
Specifies the level for parameter access. For most simple applications, the factory setting (standard) 
is sufficient. 
 
The following access levels are implemented in the converters: 
0: User defined parameter list; for details, refer to P0013 
1: Standard: permits access to the parameters needed most often 
2: Expanded: permits expanded access to converter functions/IO functions, for example 
3: Expert: only for experts 
4: Service: only for use by authorized Service; password protected