Pelco Endura GW5000 Gateway GW5000 User Manual

Page of 44
C2694M (7/08)
13
RACK MOUNTING
The GW5000 mounts into an industry-standard 19-inch (48 cm) equipment rack. The GW5000 occupies one rack unit (1.75 inches or 4.5 cm) of 
vertical rack space. The hardware necessary to mount the GW5000 into a rack is supplied with the unit.
The rack must meet the following requirements:
19-inch (48 cm) EIA-310-D compliant (rear column required).
Rack column depth: 24 to 30 inches (61 to 76 cm).
Column-mounting hole provisions: 10-32 UNF-2B threaded holes or square window holes on front and rear columns.
Door systems are acceptable. Front doors must have at least 2 inches (5.1 cm) between the GW5000 front bezel and the inside of the door. 
Rear doors may only be used on rack columns that are more than 26 inches (66 cm) deep.
To install the GW5000 in a rack:
NOTE: Figure 4 identifies each piece of hardware for this procedure.
1. If chassis mounting brackets are not attached: Attach one chassis mounting bracket to each side of the GW5000. Use three 6-32 x 0.25-inch 
Phillips flat head screws for each bracket.
Figure 7.  Attaching Chassis Mounting Brackets
2. Remove the rubber feet from the underside of the unit, if they are attached.
WARNINGS:
Secure the front and rear screws to the support rails.
Make sure the GW5000 is level.
When mounting the unit in a rack, be sure to provide proper ventilation. If adding space between units, only use solid rack panels; the 
unit uses front air intake.
ATTACH BRACKETS
AND SCREWS
(3) SCREWS
6-32 X 0.25-INCH 
PHILLIPS FLAT HEAD