6. Attach one support rail assembly to the equipment rack in the desired location (refer to Figure 10):
NOTE: The support rail assemblies are identical and may be used on either the right or left side of the rack.
a.
Position the ear of the front-mount rail against the front of the equipment rack. Align the top and bottom holes in the ear of the rail 
with the threaded holes (or cage nuts) in the rack.
b.
Using two 10-32 x 0.5-inch Phillips flat head screws, attach the ear of the rail to the front of the rack. Insert the screws from the 
outside of the rack, pointing toward the back of the rack.
c.
Adjust the rails to the correct depth of the equipment rack by sliding the rear-mount rail to the back of the equipment rack.
d.
Position the ear of the rear-mount rail against the rear exterior of the equipment rack. Align the top and bottom holes in the ear of the 
rail section with the threaded holes (or cage nuts) in the equipment rack.
e.
Using two 10-32 x 0.5-inch Phillips pan head screws, attach the ear of the rail to the rear of the rack. Insert the screws from the 
outside of the rack, pointing toward the front of the rack.
Figure 10.  Attaching Support Rails
7. Repeat step 6 for the second support rail assembly.
8. Tighten the 8-32 x 0.375-inch Phillips truss head screws that were attached to the front- and rear-mount rails in steps 3 and 4.
REAR-MOUNT RAIL
FRONT-MOUNT RAIL
(2) SCREWS,
10-32 X 0.5-INCH
PHILLIPS FLAT HEAD
(2) SCREWS,
10-32 X 0.5-INCH
PHILLIPS PAN HEAD
RACK FRONT
RACK REAR