Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 11 of 51
 Issue 1.01
The detection loop connections are made on the Loop card terminals marked LOOP. The loop card has built in
isolators so it is not required to fit additional isolators directly on the loop output. Additional short circuit isolators
should be fitted at the boundaries of each fire zone.
Reference should be made to the detector manufacturer’s data sheets and installation guides supplied with the
detector or module for information on terminal connection etc. Ensure that the devices connected to the
detection loop wiring are correctly orientated for positive and negative connections.
The detection loop cable must be stripped in accordance with the manufacturer's guidelines. The cable must be
secured to the enclosure using metal compression glands and metal locking nuts in conjunction with a metal
shake proof washer to ensure that the cable metal sheath is bonded to the enclosure. Refer to figure 7.
Figure 7: Loop and Sounder Circuit Compression Gland Details
When all bases are connected but before any devices are installed and with loop isolators linked out, the
following tests should be carried out: -
!
 
Loop short-circuit. Using an ohmmeter, check for short-circuit between +ve and -ve feeds.
!
 
Loop open-circuit. Check continuity of the +ve and -ve leads. +ve to +ve and –ve to –ve.
!
 
Loop short to earth. Check using an ohmmeter between the +ve and -ve leads and an earth connection.
Warning.
Do not undertake high voltage insulation testing on external wiring after loop devices are installed as
this could seriously damage the equipment.