Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 18 of 51
 Issue 1.01
6.
OPERATION
6.1 STATUS 
NORMAL
Under normal operation conditions, the green POWER ON light is on. The remaining status and zone window
lights are off and the LCD status is as shown below.
Figure 16: Display – Status Normal Condition
6.2 
GAINING ACCESS TO LEVEL 2 OR 3
To gain access to level 2 or 3 control buttons or menus from Status Normal condition, press any numeric button.
The display will them update as shown in Figure 17.
Figure 17: - Pass Code Request
Enter the four-digit pass code (7179) and press the enter (
) button. A pop up message will appear to confirm
that the correct pass code has been accepted or not. Should an incorrect pass code be entered, repeat the
procedure. Once the correct pass code is entered the display will then update and the control buttons become
active. Access level status will be indicated on the display top right line. Refer to Figure 18.
Figure 18: Pass Code Accepted
If there is no activity of the panel control buttons for a 5-minute period, the Access Level automatically reverts
back to normal access level 1.
6.2 FIRE 
CONDITION
When a fire is detected:
!
 
The relevant red zone alarm light flashes
!
 
The red ALARM light flashes
!
 
The alarm sounder circuits are activated (unless delays are programmed)
!
 
An audible buzzer on the panel sounds
!
 
The event printer prints out the full alarm details (when installed)
!
 
The display updates providing the user with the alarm header text, total number of alarms, zone
number and 24 character zone location text. Refer to Figure 19.