Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 31 of 51
 Issue 1.01
11. 
PROGRAMMING STANDARD & CUSTOM FEATURES
Site specific information can be configured on the control panel using two methods, directly through the panel
menu options using the key buttons or using a computer running the upload download software application,
VIPER. Information within the control panel is stored in a number of modules, which have been designed to help
programming of the panel.
Unless stated, the module descriptions located within the control panel menu structure are identical to the
VIPER application and contain the same configurable options and setting parameters.
The top-level menu options, available in both the panel and VIPER are STANDARD FEATURES and CUSTOM
FEATURES.
11.1 PANEL 
SET-UP
Panel Set-up options define the way in which the panel is configured, such as the number of loops, zones and
hardware settings. The options are generally presented as a series of questions with a list of answers to select.
On VIPER a ‘site file’ is created containing all the relevant panel settings, messages and cause / effect strategy
which is then down loaded to the control panel during the commissioning stage.
!
 
Using the panel menu, panel setup is located at Set → Standard features → Panel setup.
!
 
Using the VIPER software, panel set-up is located at Edit →Standard features →Panel setup.
The following Table 10 details the options available:
STANDARD FEATURES – PANEL SETUP
Option
Function
Company message
Allows a 2 x 24-character company name or text message to be shown on the LCD display during STATUS
NORMAL conditions and replaces the default Kidde logo.
Install logo
Set to ‘Yes’ to view the Kidde logo during STATUS NORMAL conditions. Set to ‘No’ to view the 2 x 24
character text message.
Date program last
changed
This option is automatically updated by the control panel or VIPER and indicates when the programming was
last altered.
Loop quantity
Determines the number of loop cards installed in the panel and is automatically updated during power up by
the control panel. In VIPER this option is manually adjusted to define the number of loops required by the site
file.
Protocol
Defines the type of detection protocol to be used, Apollo or Hochiki ESP. The control panel MCP card
automatically identifies the BLC card loop software protocol and updates the setting during power up. On
VIPER this option is manually adjusted to enable the correct device library (Apollo or ESP) to be loaded.
Install printer
Set to ‘Yes’ to install the main panel event printer.
Fire zones
Defines the number of fire zones used within the panel menu structure and the number of LED display cards
installed within the panel enclosure. Range available – 24 (default), 56, 88 and 120. Note: zone indications on
the Vega LT are fixed at 16.
Plant zones
Set to ‘Yes’ to install the 64-non fire related plant zones, allows access to the panel menu structure for plant
zones. Note: on Vega LT it is not possible to install the optional 64 yellow zone LED indication card.
Install repeater
Set to ‘Yes’ when installing the repeater output driver card, part number 44782-K076.
Day mode stop
Determines the automatic stop time during day mode operation. The user manually enables Day mode
operation, the pre-programmed detection is then adjusted automatically. Day mode operation will automatically
revert to normal operation at the pre-defined time.
Pre silence delay
Inhibits the operation of the silence alarms button during an alarm condition for the pre-defined time period. A
message ‘Silence inhibited for xx seconds’ appears while the timer counts down. This is a panel only
selectable option and is not available from VIPER.
Recal time
Automatic device calibration and panel system checks are performed at the pre-defined time. A fault condition
is indicated when devices fall outside normal operating thresholds or a system check fails.
LCD backlight on
Set to ‘Yes’ to permanently switch on the LCD back light display. This is a panel only selectable option and is
not available from VIPER.
Active repeater
Defines the number of active repeaters to be attached to the main control panel. Each active type repeater
panel has a unique address, which is polled by the main panel.
Repeater printer
Set to ‘Yes’ if one or more repeater panels have event printers fitted to enable additional commands specific to
printers to be transmitted.
Auto. Alarm text
Set to ‘Yes’ to automatically display the device specific information during a fire condition. The user is not
required to press the enter button (
) to view the bottom two lines of information on the display.
Latching faults
Faults displayed on the control panel are generally all non-latching. After the fault condition is corrected, the
system will revert back to Status Normal. Set to ‘Yes’ to make all faults latching.
Serial port 1
Used to interface the control panel with third party equipment such as Pager, BMS systems or with the Kidde
networks, VegaNET or CZN. This option depends upon the software version installed within the MCP card,
which provides the interface to Data Output, VegaNET, & CZN System. Refer VegaNET & CZN manual for
further details.