Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 37 of 51
 Issue 1.01
11.6.3
Activation Styles
Activation styles are used to determine how the output groups respond during an alarm condition. There are
eight different activation styles to select from when programming zones to output groups as shown in Table 15.
Activation Style
VIPER Symbol
Evacuate – Outputs operate in constant mode & timers are overridden.
E
Alert – Outputs operate in pulsed (alert) mode and include any T3 & T4 settings.
A
1
st
 device output groups operate in Alert mode, 2
nd
 device within the same zone output
groups operate in Evacuate mode and include any T3 & T4 settings.
1
1
st
 device output groups remain Silent, 2
nd
 device within the same zone output group
operate in Evacuate mode and include any T3 & T4 settings.
2
1
st
 device 1
st
 zone output groups operate in Alert mode, 2
nd
 device 2
nd
 zone (different
zone) output groups operate in Evacuate mode and include any T3 & T4 settings.
3
1
st
 device 1
st
 zone output groups remain silent, 2
nd
 device 2
nd
 zone (different zone) output
groups operate in evacuate mode and include any T3 & T4 settings.
4
Infinite Alert with T3 ignored.
5
Infinite Alert including T3.
6
Table 15: Activation Styles
11.6.4
Zone and Output Group Timers
Timers are attributed to Zones and Output Group to enable more complex evacuation cause and effect
strategies to be performed as shown in Figure 32.
Figure 32: Zone and Output Group Timers