PLANT ALARM INFORMATION
The system can accommodate up to 64 non fire related Plant Alarm zones with each zone containing one or
more loop input type devices. The plant alarm information options allow the user to define the zone specific text
descriptor and are available from the following locations:
!
 
Using the panel menu, Plant alarm info is located at Set  → Custom features → Plant alarm info
followed by the required zone number.
!
 
Using the VIPER software, Plant Alarm Information is located at Edit  →Custom features → Plant
Alarm information
.
The following Table 17 details the options available:
STANDARD FEATURES – ZONE INFORMATION
Option
Function
Text message
Plant Zone text, a 24-character text message, used to describe the location of the Plant Zone within the
installation or building.
T1
Acknowledge delay
Not applicable to Plant Zones
T2
Investigation delay
Not applicable to Plant Zones
BGU Override
Not applicable to Plant Zones
Double knock
override
Not applicable to Plant Zones
Table 17: Custom Features – Plant Alarm Information
11.12
NETWORK INFORMATION
Refer to Plug in Options section of this manual.