Kidde Fire Systems VEGA LT TM0081 User Manual

Page of 51
TM0081      
Page 47 of 51
 Issue 1.01
13  
MAINTENANCE
Maintenance of equipment external to the control panel will be detailed in the appropriate manufacturer’s
literature.
At weekly intervals a different fire detector or manual call point of the system should be tested to ensure that the
system is capable of operating under alarm conditions. Operation of the alarm sounders should be checked,
which also provides a regular reminder to those occupying the premises that there is a fire alarm system with a
particular sound. The test should be performed at a regular time to avoid confusion between a test and a
genuine fire condition.
To test the panel lights, audible buzzer and the verify the software installed within the control panel,
1.  Enter Level 2 or 3.
2.  From the Test menu select Test → Panel Test
3.  Press the enter button (
).
Make sure that all panel lights come on for five seconds and then go off and the audible buzzer sounds for five
seconds and then stops. The LCD display will perform a self-check and display the panel software serial
number. Check that the panel reverts to Level 1.
The back up batteries are maintenance free but should be replaced every 4-5 years.
The components of the control panel are designed to last for 15 years.  All printed circuit boards are self-
monitoring and therefore should only be replaced as required.
13.1  
ROUTINE MAINTENANCE
Routine maintenance should be carried out in accordance with BS 5839 Pt 1 section 6 or the relevant national
standard and any work necessary should be performed.
All performance checks undertaken should be recorded in a system logbook.
As a minimum, the following performance checks must be undertaken on each maintenance visit.
WARNING:
The static handling procedures must be adhered to and extreme caution must be exercised when
working inside the control panel due to the presence of mains voltage 230 V AC.
1.  Remove dust and dirt from the panel exterior using a soft brush or a lint cloth.  A solvent, which is
harmless to the finishes of metal and plastic, may be applied to more stubborn stains.
2.  Examine the exterior of the enclosure for any signs of damage or loose cable glands and rectify any
faults found.
3.  Remove any dust or dirt from the interior of the control panel using a soft brush or a vacuum cleaner.
4.  Examine the printed circuit boards for signs of over-heating or damaged tracks. Replace any defective
items.
5.  Examine the battery terminals for security and for signs of corrosion and replace or repair as required.
Refer to 3.5.7.
13.2 TEST 
MODE
To facilitate tests on the fire detection system the control panel can be set to operate in Test Mode using the
Test menu option. Refer to Table 9. When a detector or manual call point is triggered within the zone selected
for test, the programmed output groups are suppressed. The zone under test will be indicated on the LCD and
the test light will flash. The Zone light will operate momentarily during the activation of the loop device and will
automatically reset. Test mode is de-activated using the Test menu option.