Mitsubishi Electronics Mitsubishi Digital Electronics Electronic Accessory Q02CPU User Manual

Page of 236
 
 
 
2 - 6                                                                                                                                                       2 - 6 
MELSEC-Q
 
2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM 
 
2.2 Precaution on System Configuration 
This section describes hardware and software packages compatible with QCPU. 
 
(1)   Hardware 
(a) The number of modules to be installed and functions are limited depending on 
the type of the modules. 
Applicable Module 
Type 
Limit of number of modules 
to be installed 
Q Series MELSECNET/H 
network module 
• QJ71LP21 
• QJ71BR11 
• QJ71LP21-25 
• QJ71LP21G 
• QJ71LP21GE 
Up to 4 in total of inter-PLC 
network and remote I/O 
network modules 
Q series Ethernet interface 
module 
• QJ71E71 
• QJ71E71-B2 
• QJ71E71-100 
Up to 4 units 
Q series CC-Link system 
master local module 
• QJ61BT11 
No limit  1 
MELSECNET/MINI-S3 data 
link module 
• A1SJ71PT32-S3 
• A1SJ71T32-S3 
No limit 
(setting of automatic refresh 
function not allowed) 
AnS series special function 
module shown on the right 
• A1SD51S 
• A1SD21-S1 
• A1SJ71J92-S3 
(When GET/PUT service is used) 
Total of 6 units 
Interrupt module 
• A1SI61 
• QI60 
One unit only 
1: A maximum of 4 modules if the network parameters for CC-Link are set and 
controlled by the GX Developer. There is no restriction in the number of modules 
when the parameters are set by the special-purpose instructions for the CC-Link. 
For details on the CC-Link System Master Local Unit that can set parameters with 
the special-purpose instructions, refer to the user's manual for the CC-Link Master 
Local module. 
 
(b) When the AnS series special-function modules shown below are used, a 
limitation is given to an accessible device range. 
• A1SJ71J92-S3 type JEMANET interface module 
• A1SD51S type intelligent communication 
 
Device 
Accessible device range 
Input (X), Output (Y) 
X/Y0 to 7FF 
Internal relay (M), Latch relay (L) 
M0 to 8191 
Link relay (B) 
B0 to FFF 
Timer (T) 
T0 to 2047 
Counter (C) 
C0 to 1023 
Data register (D) 
D0 to 6143 
Link register (W) 
W0 to FFF 
Annunciator (F) 
F0 to 2047 
 
(c) A graphic operation terminal can be used only for the GOT900 series (Basic 
OS matching Q mode and communication driver must be installed). 
The GOT800 series, A77GOT, and A64GOT cannot be used.