General
The Liebert NX UPS uses intelligent and reliable 
decentralized technology to achieve parallel opera-
tion of two modules of the same rating.
The 1+1 system is used to:
• Increase the reliability of the system to ensure 
adequate power supply to the critical load con-
nected.
• Increase serviceability and allow the execution of 
maintenance operations and reparations without 
affecting the ordinary operating conditions of the 
system (depending on the redundancy level).
Conditions for Parallel System
1. Each UPS module should have the same rating, 
the same firmware and hardware version.
2. Each UPS module must have the same bypass 
source.
3. The outputs of all UPS modules are connected 
altogether.
4. The main inputs can be from different sources, but 
the phase rotation sequence of main inputs, 
bypass inputs and outputs must be correct and the 
same.
5. The parallel logic cable and load sharing cable 
must be connected in a ring correctly (See 
Features of Parallel System
1. The hardware and firmware for parallel UPS 
module operation is standard in the Liebert NX, 
and the configuration can be set up by changing 
the settings in configuration software.
2. It is easy to install the parallel cables in a ring, 
providing high reliability and redundancy. And 
the intelligent paralleling logic provides the user 
with maximum flexibility. For example, shutting 
down or starting up the UPS modules in the 
parallel system can be done in any sequence. If an 
overload transfer occurs, the whole system can 
recover automatically from bypass mode after the 
overload is cleared.
3. The total load of the parallel system can be 
queried from each module’s liquid crystal display 
screen.
4. Optional monitoring background software can 
treat the entire parallel system as a big 
single-module UPS, and provide corresponding 
management. It can also get the information for all 
modules by connecting to just one of the modules.
+
!
CAUTION
An external maintenance cabinet is strongly 
recommended to maintain the power supply to 
load in case of complete maintenance.