if they get failure during operation. For 1+1 sys-
tems, this settings needs to be set to 1.
System Startup
1. Start each UPS normally as described in Liebert 
NX installation manual. SL-25215.
2. Turn on the inverter of each UPS module one at a 
time.
3. Apply the load after the last UPS module transfers 
to inverter. The total load can be determined 
through the LCD of either UPS.
4. Verify the load rate of each UPS module. If the 
load rates are roughly the same, then the parallel 
system may be assumed to be operating normally.
Emergency Power Off (EPO)
The external emergency stop facility is identical to 
that described for the single unit installation — that 
an individual emergency stop button is provided for 
each unit. Note that this is a Normally Open switch.
Figure 3
Connecting EPO push button
NOTE
The settings should be the same for all 
modules within the parallel system, except 
the UPS ID No. 
NOTE
If one module cannot transfer to inverter 
mode long after its inverter is on, its output 
connection may not be good or its output 
phase rotation may not be coincident with 
other modules. At this time, the LCD for the 
UPS module will display “inverter 
asynchronous” and the inverter indicator 
will flash continuously. If either UPS 
module makes abnormal noise after it 
transfers to inverter, its parallel cables may 
be incorrectly connected.
EPO-H
EPO 
Monitor board
       
EPO-L
X2
       
UPS1
       
UPS2
       
EPO-H
Monitor board
       
EPO-L
X2