Component identification  17 
Item 
Component 
Description 
NA 
PLC* 
The computer located on the inside door of the control cabinet that 
controls the ECS system 
 
*These components are only installed in the IT section A control cabinet. 
IT section B control cabinet 
 
 
Item 
Component 
Description 
VESDA air sampling smoke 
detection unit 
An early warning laser scan smoke detection unit 
Fire system junction box 
Junction box to connect the IT section B fire system to IT section A 
UPS 
Provides backup power to the IT section B VESDA in the event of 
power loss to the HP POD 240e NA 
DIN rail with EPO modules 
Sends a signal to all of the connected EPO devices 
For more information, see "EPO system (on page 
)." 
DIN rail with terminals and ECS 
communication modules 
Sends information from IT section B to the PLC in IT section A 
DIN rail with terminals and fuses  Sends information from IT section B to the PLC in IT section A 
240/120V transformer 
Provides house power to IT section B for convenience outlets 
 
For more information about the specific control components within the control cabinet, see the Operations 
and Maintenance Manual for the HP Performance Optimized Datacenter 240e North America (Adiabatic). 
 
Security component identification 
The security system components are located in the hot aisle porch.