Life safety systems  19 
Life safety systems 
Life safety overview 
The HP POD 240e NA has multiple life safety systems that work together to protect the HP POD 240e NA 
equipment and personnel. The following life safety systems are included on the HP POD 240e NA: 
 
EPO system (on page 
) 
 
Fire detection system (on page 
) 
 
Emergency egress (on page 
) 
 
Facility connections to ECS ("
" on page 
) 
 
EPO system 
If the HP POD 240e NA must be shut down during an emergency, the EPO system automatically powers off 
the HP POD 240e NA, activates the EPO indicator on the ECS panel door, and changes the EPO status light 
tree that is located on the POD exterior to red. 
To be sure that all rack-mounted UPS devices are shut down during an EPO event, verify that each 
rack-mounted UPS device is connected to the HP POD 240e NA EPO system. 
The EPO system can be activated two ways: 
 
Excessive high temperature in the hot aisle—The HP POD 240e NA includes two thermisters. If both 
thermisters reach 60°C (140°F), an EPO shutdown is triggered automatically. 
Side view 
 
 
Manual initiation—To manually trigger an EPO shutdown, press any of the EPO buttons. There are EPO 
buttons located next to the personnel access doors in the POD. 
For the location of EPO buttons, see "Life safety component identification (on page 
)."