HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
Power, electrical, and controls  29 
End view shown 
 
 
Feature 
Specification 
Frequency 
60 Hz 
Amps 
125A 
Voltage 
415V, wye 
Grounding 
Copper 
Feeder conductors 
3-phase + equipment ground 
 
 
Panel schedules 
The panel schedule for each electrical panel is permanently affixed to the inside cabinet door of each 
electrical panel. 
 
Wire color code 
    
 
IMPORTANT:
  The use of UL-approved colored tape over another color of wire is only acceptable 
on wire sizes #2 and larger. 
  
120 Volt Wiring System—Power required for the transformer in control cabinets 
 
Wire color 
Description 
Black 
Single-phase current carrying conductor 
White 
Neutral 
Green or green and 
yellow 
 
Equipment grounding conductor 
 
Bonding conductor 
 
Earth ground 
 
415 Volt Wiring System—Power required for electrical busway feeders 
 
Wire color 
Description 
Brown and violet 
A Phase