HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
Power, electrical, and controls  27 
Power feeders 
  
 
IMPORTANT:
  A licensed electrician must connect the power according to all local and national 
electrical codes, and must comply with manufacturer specifications. 
  
Twenty-four power feeder couplings, twelve per IT section, provide the entrance for power to the HP POD 
240e NA. The power feeders route into the top of each electrical panel on the end of the HP POD 240e NA. 
Top view shown 
 
The twenty-four power couplings are identified as either main power couplings or Adiabatic mechanical 
power couplings. 
Main power couplings 
 
Each of the four main power panels contains four power feeder couplings, for a total of sixteen main 
power couplings. 
 
Each main power coupling has a 10.16 cm (4 in) diameter. 
Adiabatic mechanical power couplings 
 
Each of the two Adiabatic power panels contains four power feeder couplings, for a total of eight 
Adiabatic mechanical power couplings. 
 
Each Adiabatic mechanical power coupling has a 7.62 cm (3 in) diameter. 
Power feeders are sized in accordance with NEC and IEC regulations. 
 
Electrical panel labels 
  
 
WARNING:
  To avoid the risk of personal injury or loss of life, all personnel must comply with PPE 
requirements when opening or working inside areas of the HP POD 240e NA that are marked as 
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).