Environmental control system  44 
  
 
The Top screen displays the following information for each IT section. 
 
Information displayed  Description 
CA pressure 
Indicates the minimum, maximum, and average 
pressure values for each IT section 
CA RH 
Indicates the minimum, maximum, and average 
relative humidity percentages from each IT section 
CA combo temperature 
Indicates the minimum, maximum, and average 
temperature values for each IT section 
Return temperature 
Indicates the minimum, maximum, and average 
return temperature values for each IT section 
HA pressure 
Indicates the minimum, maximum, and average 
pressure values for the hot aisle 
Hot aisle temperature 
Indicates the hot aisle temperature at three different 
locations in the hot aisle. 
Min and Max value sensor 
number 
Indicates the specific sensor that is reading the 
minimum and maximum value for each statistic 
Fan speed 
Indicates the exhaust fan speed percentage