HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
Environmental control system  46 
  
 
The AD detail screen displays the following minimum and maximum alarm setpoint ranges that you can 
configure: 
 
Setpoint displayed 
Description 
HA return temperature 
Indicates the temperature reading from the hot 
aisle 
HA static pressure 
Indicates the pressure value reading from the hot 
aisle in relation to the external ambient 
temperature 
CA wall temperature 
Indicates the temperature from the wall sensor 
located in the IT sections 
CA temperature combo 
Indicates the average temperature from the wall 
sensor and discharge temperature sensor 
CA relative humidity 
Indicates the relative humidity percentage from the 
wall sensor 
CA dew point 
Indicates the dew point temperature from the wall 
sensor 
CA static pressure 
Indicates the pressure value reading from the IT 
sections in relation to the external ambient 
pressure 
CA discharge temperature  Indicates the discharge air temperature 
 
The AD detail screen displays the following operational parameters for each AHU: