Environmental control system  59 
 
Callout  Sensor 
Quantity per 
IT section 
Description 
Temperature and relative 
humidity sensors 
 
Monitor the temperature and humidity in the 
six Adiabatic zones of the HP POD 240e NA 
 
Report data to the AHU controllers 
Differential pressure sensor 
port 
 
Works in combination with the AHU sensors to 
monitor pressure in the six Adiabatic zones of 
the HP POD 240e NA 
 
Reports data to the AHU controllers 
 
HVAC sensors 
Six AHU temperature and pressure sensor probes work in combination with the differential pressure sensor 
port, callout (2) in the figure above, to calculate the cooling unit discharge temperature and average pressure 
in each IT section. This data is reported to the AHU controllers. 