Overview 
The POD AHU systems are designed to condition the air in a portable, containerized computer room, and 
are installed directly on top of the HP POD 240e NA. The HP POD 240e NA includes a total of four cradles, 
each holding 3 Adiabatic units, for a total of 12 Adiabatic units. 
The AHU system requires a potable water source and HP highly recommends installing a filter to be sure that 
water is free of particles. For more information about water requirements, see the HP Performance Optimized 
Datacenter 240e NA Site Preparation and Requirements
 Guide
 
Adiabatic components 
Each Adiabatic unit is housed in a NEMA 3 rated steel frame cabinet that is rated for outdoor use. The 
exterior of the cabinet is coated with a durable finish to protect against corrosion. Access panels are located 
on the front and on the rear of the cabinet for easy access to all of the components. The access panels are 
safety interlocked with the power disconnect switch to prevent the removal of the panel when the switch is in 
the ON position. The power disconnect switch must be turned OFF to gain access to the electrical 
compartment. 
Side view shown 
 
 
Item 
Component 
Description 
1  
Lifting eyes
*
 
For crane attachment to lift the Adiabatic unit during assembly 
2  
Inclement weather 
hood  
Prevents snow or heavy rain from entering the Adiabatic unit. The inclement 
weather hood is also equipped with a screen to prevent birds and other small 
animals from nesting in the air inlet opening. 
Access panel to the 
damper actuator 
Provides access to the damper actuator motor