HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
AHU system  64 
The bypass damper (2) and isolation damper (3) are both completely open, to optimize airflow efficiency. 
The outside air damper (1) and hot aisle return damper (4) moderate to maintain a set temperature within the 
IT sections. 
Side view shown 
 
Hot weather damper operation 
The hot aisle return damper (4) is completely closed, so that the air returning from the hot aisle is not 
recirculated through the Adiabatic unit. The outside air damper (1) and the isolation damper (3) are both 
completely open to optimize airflow efficiency. The bypass damper (2) modulates to maintain the humidity 
parameter. 
Water is added to the media to cool the outdoor air, while still maintaining the humidity in the IT sections 
below the max RH parameter. 
Side view shown 
 
Exhaust fan operation