HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
AHU system  65 
The HP POD 240e NA is equipped with 10 exhaust fans that remove heated air from the hot aisle. The 
exhaust fans feature an integrated monitoring function to protect the motor and electronics against damage 
from jamming, phase loss, or overheating. 
If any of the following failure conditions occur, the motor automatically stops and an alarm is signaled: 
 
Locked rotor 
 
Low main supply voltage 
 
Loss of a phase 
 
Over-heating of the exhaust fan electronics 
 
Over-heating of the exhaust fan motor 
For more information about the exhaust fan, see the HP Performance Optimized Datacenter 240e NA 
Maintenance and Service Guide
Side view shown 
 
 
Static pressure control 
The control of static pressure is used to be sure that the airflow from the cold aisle of the IT sections across the 
rack and into the hot aisle of the HP POD 240e NA remains constant. The pressure in the hot aisle is 
controlled to external ambient pressure, and the IT sections are slightly higher than the external ambient 
pressure. 
The static pressure is controlled to a default parameter of 0.1 in H
2
O above external ambient pressure in the 
cold aisle, which cannot be adjusted by a customer.