HP Performance Optimized Data Center (POD) 240a User Manual
Specifications 72
Specifications
General specifications
Features
Specifications
Overall dimensions
•
Height—6.74 m (22 ft 1 1/4 inches)
•
Length—13.77 m (45 ft 2 1/4 inches) including hot aisle
porch
•
Width—9.53 m (31 ft 3 inches) with cradles and hoods
installed
Weight
1
Empty—66,859 kg (147,400 lb)
Full—138,309 kg (304,920 lb)
Full—138,309 kg (304,920 lb)
Power input voltage
•
IT equipment—415/240V, 3-phase, wye, 4 wire
•
Adiabatic system—415/240V wye
Power distribution
200A electrical busways
2
Maximum rack quantity
44 racks
RUs per rack
50 RU
RU total
2,200 RU
Peak rack capacity
69.12 kW
Voltage to rack
240V
Minimum quantity of PDUs per HP POD 240e
NA
NA
44 (one per rack)
Maximum quantity of PDUs per HP POD 240e
NA
NA
88 (two per rack)
Maximum power per PDU
34.56 kW
Network supported
Bulk cable pass through fiber
Bulk cable pass through copper
(Optional) External-rated demarcation box
1
Empty weight includes the HP POD 240e NA structure, empty racks, PDUs, and drop boxes. It does not include any IT
equipment. All weights are estimates and can vary for your POD.
2
Can be configured for redundancy or non-redundancy
Rack specifications
Standard HP POD 240e NA racks (AT978A)
Feature
Specification
U height
50U
Width
54.6 cm (21.5 in)
Depth
87.6 cm (34.5 in)
Maximum load weight
1,360.7 kg (3,000 lb)