HP Performance Optimized Data Center (POD) 240a User Manual

Page of 93
 
Specifications  72 
Specifications 
General specifications 
 
Features 
Specifications 
Overall dimensions 
 
Height—6.74 m (22 ft 1 1/4 inches) 
 
Length—13.77 m (45 ft 2 1/4 inches) including hot aisle 
porch 
 
Width—9.53 m (31 ft 3 inches) with cradles and hoods 
installed 
Weight
1
 
Empty—66,859 kg (147,400 lb) 
Full—138,309 kg (304,920 lb) 
Power input voltage 
 
IT equipment—415/240V, 3-phase, wye, 4 wire 
 
Adiabatic system—415/240V wye 
Power distribution 
200A electrical busways
2
 
Maximum rack quantity 
44 racks 
RUs per rack 
50 RU 
RU total 
2,200 RU 
Peak rack capacity 
69.12 kW 
Voltage to rack 
240V 
Minimum quantity of PDUs per HP POD 240e 
NA 
44 (one per rack) 
Maximum quantity of PDUs per HP POD 240e 
NA 
88 (two per rack) 
Maximum power per PDU 
34.56 kW 
Network supported 
Bulk cable pass through fiber 
Bulk cable pass through copper 
(Optional) External-rated demarcation box 
 
1
Empty weight includes the HP POD 240e NA structure, empty racks, PDUs, and drop boxes. It does not include any IT 
equipment. All weights are estimates and can vary for your POD. 
2
Can be configured for redundancy or non-redundancy 
 
Rack specifications 
Standard HP POD 240e NA racks (AT978A) 
 
Feature 
Specification 
U height 
50U 
Width 
54.6 cm (21.5 in) 
Depth 
87.6 cm (34.5 in) 
Maximum load weight 
1,360.7 kg (3,000 lb)