HP Performance Optimized Data Center (POD) 40c User Manual

Page of 84
 
Specifications  71 
Specifications 
General HP POD 40c G2 specifications 
 
Features 
Specifications 
Overall dimensions 
 
Height—3.66 m (12 ft) 
 
Length—12.19 m (40 ft) 
 
Width—2.43 m (7.97 ft) 
Weight
1
 
Empty—16,783 kg (37,000 lb) 
Maximum fully loaded—46,266 kg (102,000 lb) 
Maximum power
2
 
600 kW HP POD 40c G2 
Power input voltage 
380 VAC to 415 VAC 
Power distribution
3
 
8 x 200 A electrical busways 
Maximum rack quantity 
20 racks 
Rack Units (RU) per rack 
50 RU 
Rack Units (RU) total 
1000 RU 
Average capacity per rack (kW) 
30 kW 
Peak rack capacity 
69 kW 
Voltage to rack 
200 VAC to 240 VAC 
Minimum quantity of PDUs per HP POD 40c G2  20 (one per rack) 
Maximum quantity of PDUs per HP POD 40c G2  40 (two per rack) 
Maximum power per PDU 
30A = 17 kW; 60A = 34 kW  
Network supported 
Bulk cable pass-through-fiber 
Bulk cable pass-through-copper 
(Optional) External rated DEMARC box 
 
1
The Empty weight includes the HP POD 40c G2 structure, empty racks, PDUs, and drop boxes. It does not include IT 
equipment. 
2
The maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c G2 is 
electrically limited to 600 kW. 
3
The HP POD 40c G2 can be configured for redundancy or non-redundancy. 
 
Electrical specifications 
Electrical busway system information 
   
Feature 
Specification 
Number of busways 
Frequency 
60 Hz 
Amps (per busway) 
200 A 
Voltage (per busway) 
380 to 415 V 
Grounding 
Copper 
Busway configuration 
3-phase + neutral + equipment ground