HP Performance Optimized Data Center (POD) 240a Quick Setup Guide
Overview 5
Overview
About this document
This document outlines the site preparation requirements for an HP Performance Optimized Datacenter 240e
NA. You must provide a qualified architectural or consulting engineering team to generate site-specific
NA. You must provide a qualified architectural or consulting engineering team to generate site-specific
documents for each HP POD 240e NA installation, including final site drawings. Your site installation design
must comply with all local and national regulations, ordinances, codes, and the specifications listed in this
document.
Safety and NEC compliance
The HP POD 240e NA is Listed to UL 69050 Part 1 and Part 22 as an Information Technology Product and
Classified in accordance with the National Electric Code NFPA 70.
The HP POD 240e NA is not habitable or suitable for human occupancy. The HP POD 240e NA is Listed as
The HP POD 240e NA is not habitable or suitable for human occupancy. The HP POD 240e NA is Listed as
a Product that provides Service Access Areas for periodic maintenance and service. Access to these areas
must be controlled and available for use only by owner-authorized and qualified personnel who are trained
must be controlled and available for use only by owner-authorized and qualified personnel who are trained
in the maintenance and service of the HP POD 240e NA components. For more information, see "HP POD
)."
IMPORTANT:
Before installing the HP POD 240e NA, consult your local AHJ for applicable
regulations and to review site-specific location guidelines. If needed, obtain any necessary
permits.
permits.
Additional considerations for safety and NEC compliance are as follows:
•
The HP POD 240e NA is Listed as an Information Technology Equipment Product to UL 60950.
•
The HP POD 240e NA is evaluated as a "non-inhabitable product" that provides "service access" areas
for customer-authorized, qualified, and trained service personnel.
•
The electrical connections of the HP POD 240e NA are evaluated as feeder connections for connection
to an existing facility. The electrical connections are not suitable as "service entrance" for connection to
the utility.
the utility.
•
The HP POD 240e NA is designed for stationary installation outdoors in a Pollution Degree 3
environment, in restricted access locations, and with field wiring terminals provided for permanent
environment, in restricted access locations, and with field wiring terminals provided for permanent
supply connections.
•
The HP POD 240e NA meets the ratings in the following table.
Feature
Specification
Category
Rated Overvoltage Category III
Protection
Surge protection device
Class
Class1
Ambient temperature
2°C to 54°C (35.6°F to 129.2°F)
Relative humidity
0% to 100% humidity
Enclosure
NEMA 3R