3-68  
••••
  Chapter 3  Paramters/Functions
Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Phase Imbalance Monitor
The Phase Imbalance Monitor function monitors the condition of the phase
imbalance on the ac line as well as the status of the phase lock loop.
Function inputs
The following table specifies the input parameters of the Phase Imbalance Monitor
function.
Variable
Description
PLL error
This is the error signal of the phase lock loop.
X axis line voltage
The demodulated, x-component of the ac line voltage.  This
variable is also used in the Phase Lock Loop function.
AC line magnitude
This is the magnitude of X axis line voltage and Y axis line
voltage
 (square root of squared sums).  It represents the
magnitude of the ac line..
Phase imbalance sqr
This signal is basic in the determination of  phase imbalance
or phase lock loop goodness for the source.  It is the filtered
sum of two squared signals.  The first is PLL error and the
second is the difference between X axis line voltage and AC
line magnitude
.
Phase imbalance ref
This signal represents the allowed amount of imbalance for
the source.  It has units of volts squared.  It includes an
allowance for noise and is compensated by the magnitude
of the ac line.
Phase imbalance avg
This signal is the amount by which Phase imbalance sqr
exceeds the allowed threshold, Phase imbalance ref.
Phs imbalance limit
Clamp threshold that the integrator
Phs imbalance time
Seconds.
Function outputs
The following table specifies the output variables of the Phase Imbalance Monitor
function.
Variable
Description
Phase imbalance int
Integrator that accumulates the amount by which the line
imbalance (variable Phase imbalance sqr) exceeds its
allowed threshold (variable Phase imbalance ref). This
variable drives the AC line transient alarm and the AC line
watchdog
 trip fault. See Faults and alarms section.
AC line loss
If the ac line drops below 10% of nominal for 5msec, AC line
loss
 will be set True, declaring that the ac line has been lost.
This variable drives the AC line transient alarm.
Diagnostic variables
The following table specifies the diagnostic variables of the Phase Imbalance
Monitor
 function.
Variable
Description
PLL proven
This boolean indicates the status of the Phase Lock Loop function. The
Phase Imbalance Monitor function has a direct effect on PLL proven.