GE General Electric Computer Accessories 2300 V User Manual

Page of 266
3-92  
••••
  Chapter 3  Paramters/Functions
Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Function description
The Minimum Speed Limit function is part of the Speed Reference Generation
function. It operates on the speed reference after the Speed Reference Reverse and
before the Critical Speed Avoidance function.
The Minimum Speed Limit function prevents the speed reference from falling below
a specified magnitude. The minimum speed magnitude is defined by parameter
Minimum speed.
Related diagrams
  Speed Reference Generation (Ovr_RfSel)
Remote Speed Reference
The Remote Speed Reference forms a speed reference signal from the remote source,
which is typically a system level controller or an adjustable analog input.
Function inputs
The following table specifies the input parameters to the Remote Speed Reference
function.
Parameter
Description
Auto analog ref sel
Selects the automatic speed reference.
Man analog ref sel
Selects the manual speed reference when Manual
speed ref sel
 is False.
Auto mode select
Selects the signal that switches the remote speed
reference between the automatic and manual
references.
The following table specifies the input variables to the Remote Speed Reference
function.
Variable
Description
Jog request
Sequencer request to jog the drive.
Function configuration
The following table specifies the configuration parameters for the Remote Speed
Reference
 function.
Parameter
Description
Speed setpoint 0
Constant speed that is the manual reference when
Manual speed ref sel is True. RPM
Manual speed ref sel
Switches between the selectable and constant sources
for the manual reference.
Remote jog speed
Jog speed that becomes the local speed reference
when Jog request is True. RPM