7. PLC2Way
Details
• $s730-761
The following status code for the PLC connected at the MJ port is stored.
Errors other than the above are stored as shown below.
Solution
1. Check the parameter setting of the PLC connected at the MJ port and the setting in the 
[Temp. CTRL/PLC2Way Comm. Setting] dialog.
2. Check the cable connection.
3. Data may be disrupted because of noise.  Fix noise.
* If you still cannot solve the error even after following the suggestions above, contact 
your local distributor.
Code
Contents
0000H
Normal
FFFFH
Timeout
8001H
Check code error
8002H
Data error
800BH
Error code received from the PLC connected at the MJ port
Buffer-full error
Parity error
Overrun error
Framing error
Break detection
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
MSB
LSB
Error
0: Bits 0 to 14 are all “0.”
1: Any bit 0 to 14 is not “0.”
Error
Details
Solution
Timeout
Although a request to send is given to the 
PLC connected at the MJ port, no answer is 
returned within the specified time.
Check 1, 2, 3 described below.
Check code error
The check code in the PLC connected at the 
MJ port response was not correct.
Check 1, 3 described below.
Data error
The code of the received data is invalid.
Check 1, 2, 3 described below.
Error code 
received
An error occurs at the PLC connected at the 
MJ port.
Refer to the instruction manual for the PLC.
Buffer full
The V7 buffer is full.
Contact your local distributor.
Parity
An error occurred in parity check.
Check 2, 3 described below.
Overrun
After one character is received, the next 
character is received before internal 
processing is completed.
Check 1, 3 described below.
Framing
Although the stop bit must be [1], it is 
detected as [0].
Check 1, 2, 3 described below.
Break detection
SD (TXD) of the PLC connected at the MJ 
port remains at the low level.
Examine the connection between SD (TXD) 
of the PLC connected at the MJ port and RD 
(RXD) of the V7 series.